Cold Room Wall Panels · 75 mm
Cold Room Wall Sandwich Panel — 75 mm
The 75 mm cold room wall panel is the second step in Jawdah's PIR cold room wall range, giving clearly more insulation than 50 mm while keeping the room walls relatively slim.
- Thickness
- 75 mm
- R-value (core)
- 3.26 m²·K/W
- U-value (core)
- 0.31 W/m²·K
- Core
- Rigid PIR

Overview
Quick answer
Jawdah's 75 mm cold room wall panel is a PIR-core sandwich panel for refrigerated and conditioned rooms. Jawdah's data sheet gives R 3.26 m²·K/W and U 0.31 W/m²·K for the core alone, about a third less heat flow than 50 mm. As general guidance it suits rooms with a moderate temperature difference, confirmed by a heat-load calculation.
Overview
What the 75 mm cold room panel offers
Jawdah's data sheet gives 75 mm an R-value of 3.26 m²·K/W and a U-value of 0.31 W/m²·K. General cold room guidance is on the cold room wall sandwich panel page.
The panel joins a rigid PIR core to two metal facings, forming a wall element that insulates, blocks air and vapour and presents a washable face. The 75 mm core places it between the slim 50 mm panel and the deeper 100 mm panel.
Moving from 50 to 75 mm is the largest single reduction in heat flow anywhere in the cold room range, which makes this thickness worth checking whenever 50 mm falls short.
Applications
Where a 75 mm cold room wall typically fits
As general guidance, a 75 mm core suits rooms with a moderate temperature difference to their surroundings: chilled stores for produce or packaged food inside a building, back-of-house walk-in rooms in supermarkets and restaurants, and controlled-temperature zones within warehouses. Jawdah does not publish a temperature range per thickness, so the heat-load calculation decides.
If the room is outdoors, in an unconditioned hall or kept much colder, compare the 100 mm and 150 mm cold room panels.
Installation
Installing 75 mm cold room walls
Set the room out on a level, prepared base so panels stand plumb and joints close fully, engage each joint completely and apply the sealant the Installation Manual specifies. Fix base and corner profiles before the ceiling panels go on, and keep the protective film on internal faces until other trades finish. Trims come from the wall flashings range.
Choosing
Ordering 75 mm cold room panels
Include room sizes, set temperature, surrounding conditions, heat-load result, internal and external faces, ceiling arrangement, floor detail, door positions and quantities. Jawdah confirms joint and sealing details and the applicable data sheet per project.
Technical
Closer look
Detailed product imagery is being prepared.
In preparationJawdah data
Data-sheet facts for 75 mm
Jawdah lists the cold room wall panel in thicknesses from 50 to 200 mm, and its data sheet gives the 75 mm thermal values below.
- Thickness: 75 mm
- Core: rigid PIR
- R 3.26 m²·K/W; U 0.31 W/m²·K, core only
- Calculated with λ = 0.023 W/m·K
- Joint and sealing system: confirmed per project
Specifications
Thermal values of the 75 mm cold room panel
Divide the 75 mm core by λ = 0.023 W/m·K and the result is R 3.26 m²·K/W; invert it for the U-value of 0.31 W/m²·K. Multiplying the U-value by the wall area and the temperature difference estimates the heat entering through the core; the refrigeration engineer then adds joints, floor, doors and air changes.
| Panel thickness | R-value (m²·K/W) | U-value (W/m²·K) |
|---|---|---|
| 75 mm | 3.26 | 0.31 |
Thermal values refer to the insulation core only and exclude surface resistances and thermal bridging.
Comparison
75 mm compared with the other cold room thicknesses
Against 50 mm, the 75 mm core lowers U from 0.46 to 0.31 W/m²·K. The next step, to 100 mm, reduces it to 0.23 W/m²·K; for the 150 and 200 mm panels, Jawdah confirms the thermal values with the quotation.
Choose 75 mm when the calculation shows it meets the room's needs; going deeper adds wall thickness and panel weight for a smaller additional gain.
| Panel thickness | R-value (m²·K/W) | U-value (W/m²·K) | Listed on |
|---|---|---|---|
| 50 mm | 2.17 | 0.46 | Jawdah's data sheet |
| 75 mm (this page) | 3.26 | 0.31 | Jawdah's data sheet |
| 100 mm | 4.35 | 0.23 | Jawdah's data sheet |
| 150 mm | Confirmed by Jawdah on request | Confirmed by Jawdah on request | Listed by Jawdah |
| 200 mm | Confirmed by Jawdah on request | Confirmed by Jawdah on request | Listed by Jawdah |
Thermal values refer to the insulation core only and exclude surface resistances and thermal bridging.
Materials
Internal and external faces at 75 mm
Jawdah offers PPGI, aluminium, stainless steel and galvanised iron facings with polyester or PVDF coating, Cloud White as standard. The internal face of a chilled store is washed often, so pick it for the cleaning regime; the external face can follow the surrounding hall or outdoor exposure.

Key facts
- Jawdah lists its PIR cold room wall panel in 75 mm on its data sheet.
- 75 mm cold room wall panel: R 3.26 m²·K/W, U 0.31 W/m²·K, core only.
- Moving from 50 to 75 mm lowers the cold room panel core U-value from 0.46 to 0.31 W/m²·K.
- Jawdah does not publish a cold room temperature range per thickness.
- Cold room panel thermal values are calculated from λ = 0.023 W/m·K and exclude surface resistances.
- Jawdah confirms cold room joint and sealing details per project.
RFQ / BOQ checklist
- Room internal dimensions and number of rooms
- Required room set temperature
- Surroundings: inside a conditioned hall, an unconditioned hall or outdoors
- Refrigeration heat-load result or target wall U-value
- Panel thickness: 75 mm
- Internal face material and coating for the cleaning regime
- External face material, coating and colour
- Ceiling arrangement and floor detail
- Door sizes, positions and penetrations
- Project location and delivery schedule
Resources
Further chapters in preparation
Technical resources
Technical documentation is being prepared for this product.
Projects using this product
Project references are being prepared.
Compatible systems
Information on compatible systems for this product is being prepared.
Our technical team can share the current information on request.Ask the technical team
FAQ
Frequently asked questions
R 3.26 m²·K/W and U 0.31 W/m²·K, from Jawdah's data sheet, calculated for the PIR core only.
When the room is kept noticeably colder than its surroundings. The 75 mm core lets through roughly a third less heat than 50 mm; a heat-load calculation confirms the need.
As general guidance, when the temperature difference is larger, the room is outdoors or the refrigeration load must be reduced further. The 100 mm panel has U 0.23 W/m²·K.
No. Jawdah does not publish cold room temperature ranges per thickness; selection is made per project.
Panels are commonly used for cold room ceilings, but the arrangement and span must be confirmed with Jawdah for each project.
It is washed often and touches stored goods or packaging, so it should tolerate the cleaning regime. Stainless steel suits strict hygiene; white pre-painted steel is common for general food storage.
No. They are core-only values that exclude surface resistances and thermal bridging; joints, doors and the floor are added in the heat-load calculation.

Next step
Request 75 mm cold room wall panels
Send the room sizes, set temperature, surroundings and heat-load result. The Jawdah team will confirm the 75 mm build-up, joint and sealing details and a quotation.